11 – 3
11.3
Installing optional signaling switches on shunt trips, closing coils, and undervoltage devices
Signals the the operating status of the shunt trip, closing coil, or undervoltage device to the BSS.
A
Snap in place
B
Disassembly
(1)
See-saw
(2)
Signaling switch
(3)
Guide
(4)
Groove
(5)
Snap-fit
1
Disengage the snap-fit
2
Pull out the signaling switch
11.4
Setting delay times on undervoltage release
Instantaneous release
(5)
B
1
2
(1)
(2)
(3)
(4)
A
short-time delayed:
instantaneous:
J1
t
d
q
80 milliseconds
t
d
q
200 milliseconds