background image

Siemens Industry, Inc.

Building Technologies  Division

P/N 315-034110-6
A24205-A334-B821

Telephone Zone Card

Installation Instructions
Model TZC-8B

INTRODUCTION

The Model TZC-8B Telephone Zone Card from Siemens
Industry, Inc., provides a way for emergency response
personnel located throughout a building to speak with one
another during emergency situations. The card is located in
any FireFinder-XLS enclosure and is connected to jacks or Fire
Fighter’s Telephone Stations located throughout the building.
Portable phones (Models PFT and PFT-P) that plug into
these jacks or Fire Fighter’s Telephone Stations (Model FTS)
can communicate to the Model FMT Fireman’s Master
Telephone located at the main enclosure or to telephones
connected to the system.

OPERATION

Each TZC-8B module provides eight telephone zones. The
TZC-8B module connects to the emergency telephones or
telephone jacks located throughout a building through the
eight telephone zones. In addition, it is also connected to
the phone riser and to the CAN bus which the system uses
to control the TZC-8B.

In normal operation, the TZC-8B monitors the inputs of the
eight zones to detect if one of the connected phones is off
hook or “jacked in”

.  When this is detected, the TZC-8B

transmits a message to the system via the CAN bus. The
system indicates the call on the front panel. Depending on
operator action, a message is sent back to the TZC-8B to
connect the zone through to the phone riser.

All the TZC-8B zone circuits are supervised for Class B
(Style Y) use only.

Controls and Indicators

The front panel of the TZC-8B contains one reset switch, 20
LEDs, and two CAN address switches as shown in Figure 1.

A reset switch is located on the top of the front panel.
Pushing the reset switch re-initializes the TZC-8B operation.

CAN

TRBL

TRBL

TRBL

TRBL

ZONE 2 ACTIVE

ZONE 6 ACTIVE

ZONE 1 ACTIVE

ZONE 5 ACTIVE

ZONE 4 ACTIVE

ZONE 8 ACTIVE

TRBL

TRBL

TRBL

TRBL

ZONE 3 ACTIVE

ZONE 7 ACTIVE

CARD FAIL

GND FAULT

CAN FAIL

RESET

POWER

TZC-8B

ONES

TENS

Figure 1
TZC-8B Telephone
Zone Card

Summary of Contents for TZC-8B

Page 1: ...through the eight telephone zones In addition it is also connected to the phone riser and to the CAN bus which the system uses to control the TZC 8B In normal operation the TZC 8B monitors the inputs of the eight zones to detect if one of the connected phones is off hook or jacked in When this is detected theTZC 8B transmits a message to the system via the CAN bus The system indicates the call on ...

Page 2: ...inated indi cates that the TZC 8B has detected a trouble on Zone 1 open circuit or short circuit ZONE 8 ACTIVE Red Normally OFF When illuminated indi cates that Zone 8 is active TROUBLE Yellow Normally OFF When illuminated indi cates that the TZC 8B has detected a trouble on Zone 8 open circuit or short circuit PRE INSTALLATION CAN Network Address Switch Set the two digit CAN network address for t...

Page 3: ...s s e l n i a t S k c a J e n o h P e t o m e R 4 0 3 J F k c a J e n o h P e t o m e R S S 4 0 3 J F l e e t S s s e l n i a t S k c a J e n o h P e t o m e R T F P e n o h p e l e T s r e t h g i f e r i F e l b a t r o P P T F P k l a T o T h s u P e n o h p e l e T s r e t h g i f e r i F e l b a t r o P 0 0 3 B F e n o h p e l e T e t o m e R r o F x o b k c a B h s u l F S 1 0 3 B F e n o h ...

Page 4: ... power LED turns ON To Connect External Wiring Loosen the screw of the terminal by turning it counterclockwise Insert the wire into the side of the terminal block Tighten the screw of the terminal block by turning it clockwise ELECTRICAL RATINGS t n e r r u C e n a l P k c a B V 4 2 0 t n e r r u C V 4 2 l a n i m r e T w e r c S x a M e n o z e v i t c a r e p A m 5 3 A m 0 8 2 t n e r r u C e n ...

Reviews: