TXP CLC Course
MAX limit value
For a MAX limit value the switching point is obtained by changing the measured
variable in relation to a maximum value, i.e. > MAX. For the MAX limit value the
> MAX signal is derived from the NOC of the switching device. Figures 10 and
11 show examples of > MAX signals for pressure and level. The > MAX signals
are assigned serial numbers of XG01 and NOT MAX signals are assigned serial
numbers of XG51.
5
NOT MAX
MAX
XG51
XG01
XG51 XG01
50
100
PSIG
PSIG
Pressure
Pressure
NCC NOC
NCC NOC
Set-point
Set-point
≥
75 PSIG
≥
75 PSIG
Pressure NOT MAX or
<
MAX
Pressure
>
MAX
Figure 10 - MAX Signal (Pressure) - XG01/XG51
NOT MAX
MAX
XG51
XG01
XG51 XG01
Level
Level
NCC NOC
NCC NOC
Level NOT MAX or
<
MAX
Level
≥
MAX
Figure 11 - MAX Signal (Level) - XG01/XG51
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
27
Summary of Contents for TXP-CLC
Page 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Page 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Page 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Page 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Page 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Page 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Page 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Page 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Page 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Page 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Page 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Page 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...