Feed-back contact switchgear (RMS)
Name: RMS
Function: Defines whether the ”SAG” feed-back message of the blown fuse in the
switchgear can be detected, and with which type of switch. Additionally it is
determined here whether the TAG-OUT function (SP/BFLO) and operating
modes other than semiautomatic can be used.
Range of values: NO--Cont. / Tag--Out no
NC--Cont. / Tag--Out no
NO--Cont. / Tag--Out yes
NC--Cont. / Tag--Out yes
Basic setting:
NO--Cont. / Tag--Out no
Meaning:
Feed-back contact
&
TAG-OUT active
⇒
RMS
Detection using NC contact
No
0
Detection using NO contact
No
1
Detection using NC contact
Yes
2
Detection using NO contact
Yes
3
Default setting: 1
Command output response in case of a fault (VBAF)
Name: VBAF
Function: Defines the response of the command outputs in the event of a fault. If
the parameter is activated the command outputs ALE and ALA will not be
deactivated when the following faults occur: Status discrepancy; Feedback error;
and / or Switchgear faulty. Can only be activated by enabling TAG-OUT via
parameter RMS.
Range of values: Not activated / activated
Basic setting:
Not activated.
MAN/AUTO changeover (MAUS)
Name: MAUS
Function: Defines whether the MAN/AUTO button in the operation window is
operable. Can only be activated by enabling TAG-OUT via parameter RMS.
Range of values: Not activated / activated
Basic setting:
activated.
TAG--OUT changeover (TOUS)
Name: TOUS
Function: Defines whether the TAG--OUT button in the operation window is
operable. Can only be activated by enabling TAG-OUT via parameter RMS.
Range of values: Not activated / activated
Basic setting:
activated.
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
16
Summary of Contents for TXP-CLC
Page 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Page 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Page 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Page 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Page 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Page 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Page 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Page 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Page 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Page 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Page 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Page 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...