TXP CLC Course
The signal must be defined (SIGDEF) on the individual level logic diagram
(function plan / YFR) that is identified with the Power Plant Identification Code
(KKS) for the equipment. The signal is then available for use as an output to the
field device. The SIGDEF and KKS must match the output channel identifier in
the parameter mask of the SIM module on the rack level location drawing for the
connection to the output point.
The output signal connection to the hardware from the CAO block must have
YL01 for the I. D. Code designation and the destination on the logic function
diagram (YFR) and a YL01 for the destination ID-code on the module parameter
mask of the SIM binary output module on the hardware diagram (YDR).
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
2
Summary of Contents for TXP-CLC
Page 5: ...TXP CLC Course 1 TXP Overview Training Center ...
Page 11: ...TXP CLC Course 2 Automation System AS620 Training Center ...
Page 19: ...TXP CLC Course 3 Industrial Ethernet Training Center ...
Page 29: ...TXP CLC Course 4 Engineering system ES680 Training Center ...
Page 45: ...TXP CLC Course 5 KKS Overview Training Center ...
Page 81: ...TXP CLC Course 6 Training Project Exercise 1 2 Training Center ...
Page 101: ...TXP CLC Course 7 BT Function Block Exercise 3 Training Center ...
Page 121: ...TXP CLC Course 8 AT Function Block Exercise 4 Training Center ...
Page 137: ...TXP CLC Course 9 CBO Function Block Exercise 5 Training Center ...
Page 145: ...TXP CLC Course 10 CAO Function Block Exercise 6 Training Center ...
Page 155: ...TXP CLC Course 11 DCM Function Block Exercise 7 Training Center ...
Page 187: ...TXP CLC Course 12 Generation Transfer Exercise 8 Training Center ...