background image

After entering the catalog number information, press

the ENTER key.  If an invalid catalog number has
been entered, the TS-MD will respond with:

and you will be asked to enter another catalog
number.

E. If a valid catalog number has been entered, the

TS-MD will prompt for the breaker switch settings. If

the circuit breaker has a long time (continuous

current) capability, the TS-MD will prompt:

or

If the long time delay is settable, the TS-MD will
respond with:

For all breakers, the TS-MD will prompt:

Enter the instantaneous setting indicated on the
circuit breaker, in amps or in multiples of the pickup
setting.

F.

After entering the breaker switch settings, you must

select the test you wish to perform.  The TS-MD will
prompt for the test to perform:

“L” - Long time or overload test

“I” - Instantaneous test

“C” - Current transformer continuity test

Item:  

TS-MD Test Set

For use with:  

Type JMKT and LMKT Trip Units

and Type JM6B, JMKB, LM6B, LMKB, MM6B,
NM6B, and PM6B Circuit Breakers.

Page 

of 

3

SAFETY INSTRUCTIONS

Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.

Universal Test Kit (TS-MD)

Caution:  Remove electrical loads from the circuit breaker to

be tested prior to performing tests.  Failure to do so
can produce erroneous results and possible electri-
cal malfunction.

TS-MD PROCEDURES

OPERATING INSTRUCTIONS

A. Remove electrical loads from circuit breaker.

B.

Plug the TS-MD test set into a grounded 120 VAC

receptacle and turn it on.  You will be greeted by the
identifying turn-on message:

C. Remove any external accessory attached via ribbon

cables from the breaker’s test port before connect-
ing the TS-MD. Connect the ribbon cable between
the TS-MD and the circuit breaker, making sure of
alignment and polarity.  After pressing ENTER, the
TS-MD will prompt:

D.

Type in the catalog number of the circuit breaker.

Siemens Energy & Automation, Inc.  TS-MD
Test Set. Press any key to continue.

Enter catalog number

XXX…NOT found.
Press any key to continue.

Enter Long Time Delay in Seconds:

Enter Instantaneous Pickup Setting:

Enter test: L-Long

I-Inst.

C-CT Cont.?

Hazardous voltage.
Will cause death or serious
injury.

Turn off and lock out all power supplying
the circuit breaker prior to cover(s)
removal or while cover(s) are removed
and when installing any internal or
external accessory.

Replace the cover(s) and shield(s)
before power supplying this device is
turned on.

Enter Continuous Current Setting in %:

Enter Continuous Current Setting in Amps:

Reviews: