3.6
Testing peripheral devices
Automatic detectors and manual call points
Test key
Testing manual call points
– Insert test key
– Wait until response
indicator flashes
– Remove test key
– Open the cover of a manual
call point with key
– Press button in completely
– Wait until response
indicator flashes
– Reclose cover
SynoLOOP
Detector tester RE6T
Testing smoke detector
Testing heat detector
– Set zones to mode ’Detector test’ (see operating menu page 63)
– Test all detectors
for a ’Test alarm’ the response indicator on the detector flashes for approx. 10 seconds
SynoLINE
OP....
OH....
HI....
Detector tester RE6
SynoLOOP
SynoLINE
Version «KAC»
Version «DIN»
Activate fire controls
Internal controls
External controls
– Make sure that the activation
causes no damage to any buil-
ding equipment
– Activate each fire control
according to the individual
system configuration and check
for correct allocation