Fire Safety & Security Products
Building Technologies
1583_o_en_−−_2
32
08.2005
2.15
Connecting SynoLOOP devices
Note: for technical details see page 109
−> list order and type of all devices (field device list)
+
−
+
−
+
−
AI340
micro terminals
AI300
− + − + − +
Response
indicator
AI340
max. 2 response indicators
L
L
−
− +
MT320A
EOL22(Ex)
collective
line
1
2
3
4
G
H
G
H
Q
R
V
W
Q
R
V
W
Z
L
M
CO NN
L
M
CO NC NO
Z
Z
Z
L
L
front end
+
−
DFB1190
24V
DC
–
Smoke/heat detectors
Flame detectors
Manual call points
In-/and output module
EOL1
control
line
or
ABI322A
APMK=2
30V/1A
30V/1A
4k75
4k75
free terminals
Output module
AB322A
APMK=2
Input module
EB322A
APMK=1
APMK=1
APMK=5
Base SO320A
OP320A
HI320A/322A
OH320A
APMK=1
DF1191/92
In-/or output module
CB320A or DC1192
APMK=3
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
+
+
+
+
+
–> set to ’SynoLOOP’
–> set to
’SynoLOOP’
Note:
Always both
in-/and output
must be used
−
+
−
+
+
−
MT320A
CB320A or DC1192
ABI322A
AB322A
EB322A
−
+
−
+
+
−
Base SO320A
− + −
rear end
+
−
SynoLOOP allows max. 128 devices
(cable max. 150
W
/ 300nF)
Loading capacity: addition of loading factor of all devices (APMK=...) shall not exceed the value of 128
details see page 110
1)
1)
1)
1) max. 64 output
modules per
system FC330A
application with explosion
hazard area see page 34
*
DM1133A
OP620A
HI62xA
OH620A
Sockel SO620A
DM1133A