32/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Recommended commissioning
22.06.2012
2.5.2 First login in the web browser
After the web server data is prepared, the LEDs "Run" and "CF Cards" are lit. The web
browser displays the following:
After you enter "Administrator" in the "User name" field and "OZW775" in the
"Password" field, click
to open the start page "Home".
When you log in for the first time, you must enter "User name = Administrator", and
"Password = OZW775".
After the first login, English is the web browser language.
No faults are present neither in the central communication unit nor the Synco devices
on the KNX network if the rectangle at the top right in the web browser is green.
2.5.3 Change password and language
You must change the user data after the first login.
The device will offer no access security if the default password is not changed.
Siemens strongly recommends to change the default password directly after the
first login.
1. Select "User accounts" to open the window with the current users (administrator
only after the first login).
First login
Notes
Security note
Workflow