42/52
Building Technologies
Bus operator unit RMZ792
CE1P3113en
HVAC Products
10 Faults
03.04.2006
•
Setting
Device list only
:
Fault status messages from non-listed bus users will be ignored.
•
Setting
All devices
:
If, at present, the fault status message from a non-listed bus user is the most severe
pending, it will
only
appear on the menu and on info page
Fault status message bus
.
The fault LED will not be lit. Acknowledgement and reset with the fault button is not
possible and must be made locally on the respective device.
10.3 Acknowledgement of faults
When pressing the flashing fault button, all faults to be acknowledged will be acknowl-
edged. Only faults of devices from the device list will be acknowledged. Acknowledge-
ment can take place from any of the menus.
•
When a device list is full, acknowledgement of faults can take up to 1 minute
•
Faults of Synco™ devices not contained on the device list
cannot
be acknowledged
10.4 Resetting
faults
Only faults of devices from the device list can be reset. In contrast to fault acknowl-
edgements, faults must be reset on an individual basis. A reset is made by pressing the
illuminated fault button.
To ensure that the fault and the reset command can be unambiguously assigned,
resetting of the current or the displayed fault can only take place on the following me-
nus:
•
On info page
Fault status message bus
of the bus operator unit
•
On menu
Fault status message bus
of the bus operator unit
•
On menu
Faults current
(faults 1…20) of the bus operator unit
•
On the
Main menu
of the bus operator unit when the faulty device has been selected
•
Locally on the faulty device (by pressing the fault button)
•
Faults of Synco™ controllers can be reset via the bus operator unit only if setting
Remote reset of fault
is activated.
Example of universal controller type RMU710:
Main menu > Commissioning > Communication > Basic settings
•
Faults of Synco™ devices not contained on the device list cannot be reset.
10.5 Deleting
faults
The fault history of a controller cannot be deleted from the bus operator unit; this is only
possible locally on the actual bus user.