24/52
Building Technologies
Bus operator unit RMZ792
CE1P3113en
HVAC Products
6 “Commissioning” menu
03.04.2006
Status messages
Description
Sorted
Device list has been successfully
sorted
Deleted
Device list has been successfully
deleted
Sorted
Device search not possible with the
current settings of area and line
6.3.1 Submenu
“Create
list”
•
When the bus operator unit is connected to plant for the first time
•
When the bus operator unit is connected to plant as a service unit
Main menu > Commissioning > Device list > Create list
Operating line
Range
Factory setting
Area 0…15
0
Line *
/
0…15
2
Start search
--- / Searched for
---
Number of devices current
0…150
0
A search is made in the network for operable Synco™ devices in accordance with the
parameters set. An existing device list will first be deleted. The search for devices is
only possible within the selected area. Settings
Area
and
Line
confine the search for bus
users to the required part of the network. This also reduces the time required for the
search to a reasonable level.
When using setting “
*
”
for the line, the search covers all lines of the required area. In
that case, the search lasts about 15 minutes and cannot be aborted.
The device search is started via operating line
Start search
.
The number of devices found is displayed by the value of
Number of devices current
.
When creating the device list, all existing devices, device names and favorite
pages will be deleted!
•
The device list can comprise a maximum of 150 devices. If a network contains more
than 150 bus users, the search will be stopped after 150 devices. On the
List informa-
tion
menu, a
List error
is shown as
List complete
•
In the case of plant with several bus operator units, only one of them can make a
search run at a time
•
A device search across all lines (
Line
=
*
) is only possible in the bus operator unit’s
own area
•
Settings
Area
and
Line
must not be changed during the device search run.
•
If a power failure occurs during a search run, or if the bus operator unit is removed
during a search run, the device list will be declared
List invalid
•
Commands are ignored as long as a device search run is in progress
•
When creating the device list, the local names of the devices will be adopted by the
list. If, subsequently, the name is changed locally on the controller, the device list will
not automatically be updated
6.3.2 Submenu
“Sort
list”
•
Sorting the device list in ascending device address order
•
Sorting the device list in ascending device name order
•
Sorting manually with the aim to have frequently operated devices at the beginning
of the list
Use
Operating lines
Caution
Notes
Use