10 DHW heating
05.02.2007
Number Text
Effect
2571
[DHW circ pump] overload
Nonurgent message.
Acknowledgement can be selected;
factory setting: “Acknowledge and reset“
2572
[DHW circ pump B] over-
load
Nonurgent message.
Acknowledgement can be selected;
factory setting: “Acknowledge and reset“
2573
[DHW circ pump] no flow
Nonurgent message; must be acknowl-
edged and reset
2574
[DHW circ pump B] no flow
Nonurgent message; must be acknowl-
edged and reset
2575
[DHW circ pump] fault
Urgent message; must not be acknowl-
edged. Plant stop DHW
10.13 Diagnostic values
Main menu > DHW > Inputs/setpoints
Operating line
Adjustable values / display / remarks
Act value prim FT
…°C
Event logger 1
…°C
[DHW primary pump] overload
0 / 1 (1 = overload)
[DHW primary pump B] overload
0 / 1 (1 = overload)
Primary pump flow signal
0 / 1 (1 = flow)
Flow temp sec actual value
…°C
Flow temp sec setpoint
…°C
Flow signal
…°C
[DHW sec pump] overload
0 / 1 (1 = overload)
DHW plant type
0 / 1 (1 = overload)
Secondary pump flow signal
0 / 1 (1 = flow)
Act value strge tank temp top
…°C
Act value strge tank temp bott
…°C
Storage tank temp setpoint
…°C
Actual value return temp
…°C
Return temperature max
…°C
Forced charging
0 / 1 (1 = forced charging input)
Flow temp cons actual value
…°C
Flow temp cons setpoint
…°C
[DHW circ pump] overload
0 / 1 (1 = overload)
[DHW circ pump B] overload
0 / 1 (1 = overload)
Circulating pump flow signal
0 / 1 (1 = flow)
DHW optg mode
0 / 1 (1 = external selection of operating
mode)
Special day input
0 / 1 (1 = Special day input active)
Holiday input
0 / 1 (1 = Holiday input active)
Main menu > DHW > Outputs
Operating line
Adjustable values / display / remarks
Mixing valve position primary
0…100 % (3-position and modulating)
Off / On
Primary pump B
Off / On
Mix valve pos maint sec temp
0…100 % (3-position and modulating)
Secondary pump
Off / On
Secondary pump B
Off / On
Faulty circulating pump
Inputs / setpoints
Outputs