134/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
9 Heating circuit control
05.02.2007
Boost heating is activated when a change is made from room operating mode Economy
or Protection to Comfort or Precomfort
and
when the room temperature lies
0.25 K or more below the setpoint.
31
31
D
37
TR
TRSetpt
TR
SetptCmf
SetptEco
SetptTR
TR Room
temperature
TRSetpt
Room temperature setpoint
SetptCmf
Setpoint, room operating mode Comfort
or
Precomfort
SetptEco
Setpoint, room operating mode Economy
or
Protection
Δ
SetptTR
Setpoint increase
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit 1
(or
2
or
3
)
> Optimizations/influences
Operating line
Range
Factory setting
[Boost heating] setp increase
0…20 K
5 K
9.8
Limit and protective functions
9.8.1
Maximum limitation of the room temperature
If a room temperature sensor is connected, maximum limitation of the room tempera-
ture can be activated.
In contrast to room temperature influence with modulating action on the flow tempera-
ture setpoint, maximum limitation of the room temperature works with 2-position control.
When the actual room temperature exceeds the room temperature setpoint by the
adjustable room limitation increase, the heating circuit pump will be deactivated.
When the pump is deactivated, the heating circuit does not call for heat.
When the actual room temperature drops below the switch-off point by the room tem-
perature’s switching differential, the heating circuit pump will be activated.
Settings
Deactivation
⇒
Activation