5.5
Remote setpoint adjuster, absolute
The absolute remote setpoint acts on setpoints of the universal controller of the
RMS705B.
Setpoint sources BSG21.1 (0...1000
) and BSG61 (0…10 V) are ideal for room
unit QAA25 (5...35 °C).
The absolute remote setpoint acts on both Comfort and Economy setpoints.
5.5.1
Activate function
The function is activated by setting the identifier of an input as a remote setpoint. At
the same time, specify the controller (1…3) the remote setpoint should act on.
Main menu > Commissioning > Extra configuration > Input identifier >
Configuration
Operating line
Adjustable values / Comment
…X…
Activate the function by assigning the following value to
the input:
[Controller 1] rem setp adj (Rem-w1),
[Controller 2] rem setp adj (Rem-w2)
or
[Controller 3] rem setp adj (Rem-w3).
5.5.2
Type and measuring range
You can select if the remote setpoint is to be an active (DC 0…10 V) or passive
signal (0...1000
Ω
).
In addition, you can set the input signal's range:
"Value high": Value at DC 10 V
or
at 1000
Ω
"Value low": Value at DC 0 V
or
at 0
Ω
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line
Range
Factory setting
Type
0…10 V, Ohm
Ohm
Value low
Depending on selected type
Type-dependent
Value high
Depending on selected type
Type-dependent
38 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Inputs
01.04.2010