12.3 Universal fault inputs (1…20)
RMS705B provides function block "Faults" with 20 universal fault inputs. Any type
of analog
or
digital signal can be connected to these inputs.
Connections
Main menu > Commissioning > Extra configuration > Faults >
Configuration
Operating line
Adjustable values / Comment
Fault input 1
---, N.X1, N.X2, ...
...
Fault input 20
---, N.X1, N.X2, ...
Settings
The following settings are possible for each fault message:
Fault status message delay: Elapsed time until a pending fault generates a fault
message.
Fault acknowledgement
Fault priority
Limit value fault on: Limit value from which the fault message is generated.
Limit value fault off: Limit value for the normal state.
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Faults > Fault input 1...20 >
Operating line
Range
Factory setting
Fault status message delay 00.00...59.59
m.s
00.05
m.s
Fault acknowledgement
None, Acknowledge,
Acknowledge and reset
None
Fault priority
Urgent, Not urgent
Not urgent
Limit value fault on
Depending on selected type.
Type-dependent.
Limit value fault off
Depending on selected type.
Type-dependent.
If the upper and lower limit of a measured value is to be monitored, the signal is
must be sent to 2 fault inputs.
Notes
For monitoring, set the lower limit "Limit value fault on" to lower than "Limit value
fault off". This generates a fault message when the measured value is lower
than the "Limit value fault on".
The difference between "Limit value fault on" and "Limit value fault off"
represents the hysteresis.
No fault message is generated if value "Limit value fault on" is equal to "Limit
value fault off".
Adjust the texts for the universal fault inputs via the operator unit.
Fault texts
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Faults > Fault input 1...20 >
Operating line
Range
Factory setting
Fault text 1
Max. 20 characters
[Fault inp 1] fault
178 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Faults
01.04.2010