10.3 H/C demand application examples
10.3.1 Overview
RMS705B as universal device can assume functions
or
partial functions of a
consumer, primary controller, or generation.
Application
This results in sophisticated configurations and settings of the corresponding
distribution zones via the Communication menu.
The section explains the various applications and the required configuration and
communication settings to transmit H/C demand.
RMS705B can generate or evaluate demand signals for the following applications:
Consumers (Section 10.3.3).
Primary controllers (Section 10.3.4).
Generation (Section 10.3.5).
Consumers and primary controllers (Section 10.3.6).
Consumers and generation (Section 10.3.7).
The following examples are for hot water networks (heat distribution zone).
However, they equally apply to chilled water networks (refrigeration distribution
zone).
Note
10.3.2 Setting rules
Controllers (controllers 1…3, primary controller) on the H/C demand block are
enabled (shown as a cross in the configuration diagrams) if the controller's demand
is to be passed on.
RMS705B as consumer
Demand from controllers 1, 2
or
3 is to be passed on (to bus, to digital (d, Q)
or
analog (a, Y) output).
RMS705B as primary
controller
Primary controller demand is to be passed on to the bus.
149 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
H/C demand, H/C changeover
01.04.2010