10.2 Refrigeration demand function
10.2.1 Purpose and enabling
The "Refrigeration demand" function acquires refrigeration demand from various
zones via the bus. The acquired refrigeration requests can be routed to another
zone
or
further handled as a resulting setpoint condition (temperature request
signal, chilled water flow setpoint) as a continuous or digital signal.
Purpose
Contrl.
To enable function "Refrigeration demand", assign the load signal of a controller,
enable the primary controller
or
assign output Q, d, Y, a.
Enabling
10.2.2 Use universal controller as consumer
Use "Extra configuration > Aggregates > Refrigeration demand" at the
corresponding controller for a sequence of the controller to generate refrigeration
demand (see Section 10.3 for application examples).
Purpose
Contrl.
X
Main menu > Commissioning > Extra configuration > Aggregates > Refrigeration demand >
Configuration
Operating line
Adjustable values / Comment
Controller 1
---, Sequence 4
Controller 2
---, Sequence 4
Controller 3
---, Sequence 4
This allows for generating a refrigeration demand signal that can be used by
another device on the KNX. To do this, set a "Refrigeration distribution zone".
Main menu > Commissioning > Communication > Distribution zones >
Setting values
Operating line
Range
Factory setting
Refrigeration distribution zone
1…31
1
143 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
H/C demand, H/C changeover
01.04.2010