9 Signal
converter
9.1
Min-max-average
"Min-Max-Average" executes the following calculations from the signals from inputs
1 to 5:
Purpose
Selection of minimum input signal (Min).
Selection of maximum input signal (Max).
Calculation of average value (Avr).
2 "Min-Max-Average" blocks are available:
The calculated values are provided as DC 0…10 V signals (Y) and internal, analog
signals (a).
The calculations do not consider non-configured inputs.
Note
9.1.1
Enable Min-Max-Average
Assign an input to enable this function.
Main menu > Commissioning > Extra configuration > Signal converter > Min-Max-Average
1…2
Configuration
Operating line
Adjustable values / Comment
Factory setting
Input 1
---, N.X1, N.X2, ...
Input 2
---, N.X1, N.X2, ...
Input 3
---, N.X1, N.X2, ...
Input 4
---, N.X1, N.X2, ...
Input 5
---, N.X1, N.X2, ...
Inputs split
Yes, No
No
Min-Max-Average A
---, N.Y1, N.Y2, ... /
enable modulating output.
Function output A
Minimum, Maximum, Average
Minimum
Min-Max-Average B
---, N.Y1, N.Y2, ... /
enable modulating output.
Function output B
Minimum, Maximum, Average
Minimum
The calculations are carried out separately for the function ranges A and B if
parameter "Inputs split" is enabled (Yes).
Inputs split
–
Function range A: Inputs 1 and 2.
–
Function range B: Inputs 3 to 5.
The calculations are carried out on all configured inputs if "Inputs split" is
disabled (factor setting No).
127 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Signal
converter
01.04.2010