Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Factory setting
Speed start condition 1 Speed 1, Speed 2
Speed 1
Speed start condition 2 Speed 1, Speed 2
Speed 1
Control switch on a panel acting directly on the motors (one separate control switch
per motor).
Example
Preselection of the speed start condition allows for defining the input value.
An analog signal can be used as start or stop signal.
The limit values for when the corresponding motor is to be switched on or off can
be set via setting values "[Start value x] On" and "[Start value x] Off".
Main menu > Commissioning > Settings > …
or
Setting values
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Factory setting
[Start value 1] on
Depending on selected type.
Type-dependent.
[Start value 1] off
Depending on selected type.
Type-dependent.
[Start value 2] on
Depending on selected type.
Type-dependent.
[Start value 2] off
Depending on selected type.
Type-dependent.
[Stop value 1] on
Depending on selected type.
Type-dependent.
[Stop value 1] off
Depending on selected type.
Type-dependent.
[Stop value 2] on
Depending on selected type.
Type-dependent.
[Stop value 2] off
Depending on selected type.
Type-dependent.
8.4.13 "On" by outside temperature
At low outside temperatures, motors can be run continuously to control a pump to
e.g. prevent water from freezing in pipes.
This function is available in 1-speed and twin motors.
Note
The function can be enabled only if there is an outside temperature value
(Section 5.6 "Outside temperature").
You can disable the function by setting "Outside temp-dependent ON" to "---".
In twin motor operation, the motor with the current run priority is switched on.
If the outside temperature drops below the set limit value, the RMS705B switches
on the motor of the circulating pump. The motor is switched off when the outside
temperature exceeds the limit value by 2 K.
Example
Main menu > Commissioning > Settings > …
or
Setting values
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Factory setting
Outside temp-dependent ON
50...
250 °C, ---
- - -
If the function is active and if there is a outside temperature sensor error, the motor
is switched on permanently.
Note