Flow signal
V
Flow supervision can be provided by a flow switch
or
flow sensor.
Main menu > Commissioning > Extra configuration > Aggregates > Motor > Motor 1...6 >
Operating line
Adjustable values / Comment
Flow signal
---, N.X1, N.X2,...
(digital and analog* inputs).
*) With analog inputs, only inputs with units m/s, bar, mbar, Pa, Universal 000.0, Universal 0000 are
possible.
A fault message is triggered and a fault issued at output "Flow delay start" if you
want to switch on the motor and if there is no checkback after a set time ("Motor
fault").
Since measurements can fluctuate during operation, a delay time can be set ("Flow
delay operation"). A fault message is triggered and a fault indicated at output
"Motor fault" if a flow signal fault occurs during operation.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Factory setting
Flow delay start
00.00...59.59 m.s
02.00 m.s
Flow delay operation
00.00...59.59 m.s
00.05 m.s
The switching values for the flow signal fault can be set.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Factory setting
Flow switching value on
Depending on selected type.
Type-dependent.
Flow switching value off
Depending on selected type.
Type-dependent.
The motor is switched off if there is a flow fault with 1
or
2-speed motors. One of
the following fault messages is displayed.
You can change the following texts ex-works texts in the RMS705B at the
password level.
No. Text
Effect
1312
[Motor 1] no flow
Urgent message; must be acknowledged and reset.
1322
[Motor 2] no flow
Urgent message; must be acknowledged and reset.
1332
[Motor 3] no flow
Urgent message; must be acknowledged and reset.
1342
[Motor 4] no flow
Urgent message; must be acknowledged and reset.
1352
[Motor 5] no flow
Urgent message; must be acknowledged and reset.
1362
[Motor 6] no flow
Urgent message; must be acknowledged and reset.
Configuration
Setting values
Setting values
Fault messages
1
or
2-speed motor