Remote Monitoring, Service Channel, and IP Network
RM with Analog Interface
The Remote Monitoring (RM) function offers the option of accessing equipment data at the SWT 3000 via a
USB connection with the service PC. With RM, it is possible to transmit equipment data between the terminals
of one or more transmission routes. Transmission is possible in both directions.
[dwrm4swt-040711-01.tif, 1, en_US]
Figure 2-16
RM Communication between Connected SWT 3000 Units
↔
Protection signal transmission path
USB
Local interface
SSB
Remote monitoring interface
RM
Inband RM-Channel
////
4-wire link
The SWT 3000 unit in station 1 can read out the event memory of the SWT 3000 unit in station 2, if an RM is
adjusted via PowerSys with a service PC.
For this purpose, the units are assigned an RM address and a master-slave connection must be configured.
RM communication over several transmission routes is also possible by connecting 2 units via the remote
monitoring interface (SSB).
[dwcomswt-050711-01.tif, 1, en_US]
Figure 2-17
Communication over 2 SWT 3000 Connection Routes
2.10
2.10.1
Functional Description
2.10 Remote Monitoring, Service Channel, and IP Network
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
67
C53000-G6040-C605-1, Edition 03.2020