Common System Data
Power Supply
Input voltage
DC 24 V to 60 V (-20 % / +20 %) or
DC 110 V/220 V/250 V (-20 % / +20 %) or
AC 115 V/230 V (-20 % to +10 %) 47 Hz to 63 Hz
Power consumption
Approx. 30 W/VA
Cable cross-section
Max. 2.5 mm
2
Characteristic
Conditions
MLFB: 7VR9514/CC
MLFB: 7VR9515/CC
Input voltage range U
I
AC
DC
-
DC 19.2 V to 72 V
AC 85 V to 264 V
DC 88 V to 300 V
Input voltage nominal
DC
24 V, 48 V, and 60 V
110 V, 220 V, and 250 V
Input current
U
nom
≤ 3.9 A
≤ 1.2 A
Input fuse
18
slow-blowing
6.3 A
6.3 A
Alarm Output ALR Module
Contact type
Relay CO, changeover
Contacts per module
3
Switching power
300 W
1000 VA
Switching voltage
DC 250 V or AC
Carry current
DC 5 A or AC
Binary Input ALR Module
Nominal voltage BI1/BI2
DC 24 V to 250 V (-20 % to +20 %)
Polarity
Independent
Clock-Synchronization Input
Sync Pulse
Min/hour
IRIG-B
B00x, B000, B004
Ethernet
Network Time Protocol (NTP)
Nominal voltage binary input
DC 24 V to 250 V (-20 % to +20 %)
Nominal voltage IRIG-B input
DC 5 V, DC 12 V, and DC 24 V
Event Recorder
Events
8192
Non volatile
1 ms time resolution
Trip counter
Individual counter for each received and transmitted command
Size 128
14.6
18
The fuse must have a safety certification for DC voltages.
Technical Data
14.6 Common System Data
376
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020