Synco™ living

Radiator Control Actuator

SSA955

RF-controlled actuator for radiator valves

RF communication based on KNX standard (868 MHz, bidirectional)

Battery-powered by commercially available 1.5 V batteries
(reversed polarity protection)

Low power consumption

Silent mode (e.g. for use in sleeping rooms)

Nominal stroke 2.5 mm

Valve positioning force 110 N

Automatic identification of valve stroke

Parallel connection of multiple actuators possible

Integrated temperature sensor

For direct mounting with coupling nut (no tools required)

Manual adjustment

Summary of Contents for SSA955

Page 1: ... Battery powered by commercially available 1 5 V batteries reversed polarity protection Low power consumption Silent mode e g for use in sleeping rooms Nominal stroke 2 5 mm Valve positioning force 110 N Automatic identification of valve stroke Parallel connection of multiple actuators possible Integrated temperature sensor For direct mounting with coupling nut no tools required Manual adjustment ...

Page 2: ...w rate of chilled water 5 30 C through the fully opened valve H100 at a differential pressure of 100 kPa 1bar The SSA955 can operate without adapter radiator valves of other manufacture provided they have a connecting thread M30x1 5 mm and meet the following requirements Requirements placed on valves of other manufacture Force 100 N nominal Fully closed x 9 0 mm Fully open y 14 5 mm 90187 y A F M3...

Page 3: ...e reference Radiator valves and adapters if required must be ordered as separate items Each SSA955 is supplied complete with alkaline batteries and Mounting Instructions Product documentation The Operating and Commissioning Instructions for the SSA955 are contained in the product documentation of the central apartment unit Functions T M SSA955 ƒ 2700B01 ƒ Radiator Synco 900 central unit Room contr...

Page 4: ... extremely quiet operation is required the SSA955 can be switched to low noise operation from the central apartment unit Summer operation is triggered from the central apartment unit When the SSA955 receives a command to start summer operation the radiator valve will be opened or closed depending on the position demanded by the central apartment unit The antilime function is triggered by the centr...

Page 5: ...g and indicating elements 2700Z07 Multifunction LED Manual adjustment Multifunction button Overview of functions of the indicating and operating elements of the SSA955 Multifunction LED Multifunction button Manual adjustment Battery state Binding state Binding process Calibration state Calibration process Lead controller Battery state query RF connection test Binding Calibration Disconnect device ...

Page 6: ... 2700Z11 60 mm Actuator and valve are joined by a coupling nut with no need for using tools The SSA955 is supplied with the stem fully retracted to facilitate mounting Mount the SSA955 first and then insert the batteries 2700Z08 Prior to commissioning check to ensure that the SSA955 is correctly fitted to the valve and that the batteries are correctly inserted For more detailed information about c...

Page 7: ...ult the SSA955 can be driven to any position using a 3 mm hexagonal socket wrench 2700Z06 3 mm The SSA955 cannot be repaired It must be replaced as a complete unit Disposal The device is considered an electronics device for disposal in terms of European Directive 2012 19 EU and may not be disposed of as do mestic garbage Dispose of the device through channels provided for this purpose Comply with ...

Page 8: ...ial commercial and light industrial environments Product standard EN60730 x EU Conformity CE A5W90000894 1 RCM Conformity A5W90000909_A 1 EAC Conformity Eurasia Conformity Safety class III to EN 60730 1 Housing IP401 to EN 60529 Degree of pollution 2 to EN 60730 1 The Environmental product declaration CE1E2700en 1 provides information on environmentally compatible product design and assessment RoH...

Page 9: ...tic conditions class 3K5 class 2K3 class 1K3 Temperature 0 50 C 25 70 C 20 65 C Humidity 5 95 r h 95 r h Humidity 5 95 r h noncondensing 95 r h 5 95 r h Mechanical conditions class 3M2 class 2M2 class 1M2 Elevation above sea level min 700 hPa corresponding to max 3000 m above sea level Dimension Dimensions in mm 75 4 95 80 6 48 2700M01 75 6 Environmental conditions ...

Page 10: ...9 Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6300 Zug Switzerland Tel 41 58 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2017 Technical specifications and availability subject to change without notice ...