Engineer Programming Via the Keypad
80
Siemens Building Technologies
Fire Safety & Security Products
09.2008
10.12.5 Soak Test
A Soak Test provides a method of putting selected zones on test. Zones on soak
test do not cause any alarms but are recorded in the event log. Zones on soak test
will remain on soak test until the soak test timer expires as in the timers default (14
days).
To perform a soak test:
1.
Scroll to the SOAK TEST programming option.
2.
Press SELECT.
3.
Toggle between ENABLE SOAK and CANCEL SOAK for preferred option.
4.
Scroll to preferred zone and press SELECT.
Î
A message confirming that the zone is in soak is displayed.
10.12.6 Audible Options
The Audible Options setting provide Tests.
To set the audible options:
1.
Scroll to the AUDIBLE OPTIONS programming option.
2.
Press SELECT.
3.
The following options are available:
–
Keypad
–
All
–
Ext Bell
–
Int Bell
4.
Press BACK to exit the Audible Options menu.