7PG2113/4/5/6 Solkor Description of Operation
4.5
Current Protection: Cold Load (51c)
The setting of each shaped overcurrent element (51-n) can be inhibited and alternative ‘cold load’ settings (51c-n)
can be applied for a period following circuit switch in.
The Cold Load settings are applied after the circuit breaker has been open for longer than the
Pick-Up Time
setting.
Following circuit breaker closure the ‘cold load’ overcurrent settings will revert to those defined in the Phase
Overcurrent menu (51-n) after either elapse of the
Drop-Off Time
setting or when the measured current falls
below the
Reduced Current Level
setting for a time in excess of
Reduced Current Time
setting.
During cold load settings conditions any directional settings applied in the Phase Overcurrent menu are still
applicable.
A CB ‘Don’t Believe It’ (DBI) alarm
condition, see 5.3 C
acted on, causing the
element to remain operating in accordance with the relevant 51-n settings. Where the
Reduced
Current
setting is set to
OFF
reversion to 51-n settings will only occur at the end of the
Drop-Off
Time
. If any element is picked up on expiry of
Drop-Off Time
the relay will issue a trip (and lockout if
a recloser is present).
If the circuit breaker is re-opened before expiry of the
Drop-Off Time
the drop-off timer is held but not reset.
Resetting the timer for each trip could result in damaging levels of current flowing for a prolonged period during a
rapid sequence of trips/closes.
Cold load trips use the same binary output(s) as the associated 51-n element.
1
1
General Pickup
51-n
51c-n Setting
51c-n Charact
51c-n Time Mult
51c-n Follower DTL
c
51c-n Reset
Cold Load
Enabled
L1 Dir En
L2 Dir En
L3 Dir En
Disabled
51c-n Min. Operate Time
Reduced
Current
Enabled
Disabled
51c-n Delay (DTL)
CB Open
CB Closed
Pick-up Time
Drop-off Time
Reduced Current DTL
Reduced
Current Level
c
<
IL1
IL2
IL3
51c
See Delayed
Overcurrent
(51-n)
1
&
S
R
Q
&
&
&
CB
Open
CB
Closed
c
Pickup
trip
c
Pickup
trip
c
Pickup
trip
<
<
Figure 4.5-1 Logic Diagram: Cold Load Settings (51c)
©2010 Siemens Protection Devices Limited Chapter 1 Page 50 of 80