7PG2113/4/5/6 Solkor Applications Guide
1.5.1 Description of Typical Setting file.
1.5.1.1
Relay Binary Inputs
Reference
(e.g. I1 =Binary
Input 1)
Connection Description
I1
Energised from Solkor R/Rf
module contact.
This triggers indication and a waveform record regardless of
the Guard relay/Trip.(A separate contact is wired externally via
a Guard contact for the trip circuit.)
I2
Energised from Guard
Override panel switch
(latched)
The switch must also short the external guard contact to allow
removal/switch off of relay DC
I3
Backup OC/EF Inhibit from a
panel switch (latched)
Mapped as an inhibit on 51-2
1.5.1.2
User Logic
Reference Setting
Description
V1
50-1 or 50G-1 Guard elements
operated
This is used to generate the Trip indication for 87L+Guard or
87L+ Guard Override
E1 I1.!V1.!I2
87L without Guard when Guard Override is not raised
Used to indicate a possible pilot open circuit, (Low level faults
below the guard setting may cause nuisance indications)
E2 (I1.V1)+(I1.I2)
Indication of trip condition, (87L and Guard operation) or (87L
when Guard Override is raised).
This is an indication of trip condition, it is used to start
Waveform Recorder and Fault Record. It is also operates
the Trip output contact used by Backup OC/EF although it
is expected that the main trip will be direct from the Solkor
R/Rf module output contactor via a Guard contact/guard
override switch connected externally
1.5.1.3
Relay Binary Outputs
Reference
(e.g. O1 =Binary
Output 1)
Setting Description
O1 Protection
Healthy
O2
Guard Relay Operated
(50-1 & 50G-1) & also
Guard Override
This is the main Guard contact for the trip circuit
O3
87L Solkor operated
This is for alarm/test only
O4 Backup
Overcurrent,
Earth Fault & E2
(=87L+Guard or
87L+Guard Override))
This is the trip output which starts a Fault Record
O5 E1
(=87L
without
Guard)
This gives an alarm that the Solkor has tripped without the Guard
This could indicate pilot open circuit
(note that a fault occurs below the Guard setting but above the Rf
setting will create an alarm)
©2010 Siemens Protection Devices Limited
Chapter 7 Page 9 of 49