7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 32 of 42
2.12 51V Voltage Controlled Overcurrent
2.12.1 Reference
Parameter
Value
Vs
Setting 60V
m
multiplier 0.5
Is
Setting 1xIn
2.12.2 Operate and Reset Level
Attribute
Value
V
op
Operate level
100 %
Vs
,
±
1 % or ± 0.25V
Reset level
≤
105 %
V
op
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz
to
f
nom
+ 2 Hz
harmonics to
f
cutoff
≤
5 %
Operate and Reset Time
As per Phase Fault Shaped Characteristic Element (ANSI 51).
Where Pickup Level = Is for Voltage > Vs
Pickup Level = (Is x m) for Voltage < Vs