7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 23 of 42
2.9
51 Time Delayed Overcurrent
2.9.1 Reference
Parameter
Value
Is
Setting
0.05, 0.06… 2.5
xIn
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
Tm
Time Multiplier setting
1.0
t
d
Delay setting
0, 0.01… 20 s
t
res
Reset setting
ANSI DECAYING, 0, 1… 60 s
IDMTL 2 to 20 x ls
I
Applied Current
(for operate time)
DTL 5 x Is
2.9.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
105 %
Is
,
±
4 % or
±
1%
In
Reset level
≥
95 %
I
op
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
2.9.3 Operate and Reset Time
Attribute
Value
Starter operate time (
≥
2
xIs
) 20
ms,
±
20ms
char
= IEC-NI,
IEC-VI,
IEC-EI,
IEC-LTI
[ ]
Tm
K
t
Is
I
op
×
−
=
1
α
,
±
5 % absolute or
±
30 ms,
for char = IEC-NI : K = 0.14,
α
= 0.02
IEC-VI : K = 13.5,
α
= 1.0
IEC-EI : K = 80.0,
α
= 2.0
IEC-LTI : K = 120.0,
α
= 1.0
char
= ANSI-MI,
ANSI-VI,
ANSI-EI
[ ]
Tm
B
A
t
P
Is
I
op
×
⎥
⎥
⎦
⎤
⎢
⎢
⎣
⎡
+
−
=
1
,
±
5 % absolute or
±
30 ms,
for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02
ANSI-VI : A = 19.61, B = 0.491, P = 2.0
ANSI-EI : A = 28.2,
B = 0.1217, P = 2.0
t
op
Operate time
char
= DTL
t
d
,
±
1 % or
±
20ms
ANSI DECAYING
[ ]
Tm
R
t
Is
I
res
×
−
=
1
2
,
±
5 % absolute or
±
30 ms,
for char = ANSI-MI : R = 4.85
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
Reset time
t
res
t
res
,
±
1 % or
±
20ms
Repeatability
±
1 % or
±
20ms
Overshoot time
< 40 ms