Scale parameters and functions
8.8 DR 7 Process interfaces
SIWAREX WP251
94
Manual, 12/2015, A5E37203357A
8.8.12
Output value following fault or SIMATIC STOP
With the default settings, the analog output is switched off following a module fault (operating
error) or at a SIMATIC S7-1200 CPU STOP.
If the analog output is, for example, to be set to 3.5 mA following a fault, this is defined using
this parameter. The current value to be output is entered in mA.
NOTICE
System can be switched to unsafe state
If the analog output is to be set to a given value following a fault (operating error), you must
ensure that this poses no danger.
8.8.13
Trace recording cycle
The trace function is used for the continuous recording of measured values. The recording
rate is defined with the parameter.
Function code
Response
1
Recording every 10 ms
10
Recording every100 ms
100
Recording every 1000 ms
1000
Recording every 10000 ms
8.8.14
Trace storage method
This parameter is used to specify the response of the trace memory.
Value
Response
0
Trace recording runs as circulating memory
1
Trace recording is stopped when memory is full and a technology message is output.