Weighing Functions
SIWAREX FTA
5-95
Table 5-15
Tolerance information evaluation
5.16 DR 23 Scale parameter 2 (AWI)
Weighing parameters are held in DR23. These are normally typical to the scale
and do not depend heavily on the changing material properties within a limited
extent. Procedure:
o
Adjust all parameters corresponding to their purpose
o
Send DR 23 to the scale
o
If required, check parameters using tests
Name
Type
Address
Default
Range of Values / Explanation
Reference
Scale parameter 2
0
Text selection for
automatic logging
BYTE
DBB000
1
0:
No autom. logging after the
weighing procedure
1:
autom. logging with text 1
2:
autom. logging with text 2
3:
autom. logging with text 3
4:
autom. logging with text 4
Other definitions not permitted.
Reserve 1
BYTE
DBB001
0
Reserve 1
Filter depth of average
value filter for dosing
WORD
DBB002
0
0 …250
0: average value filter deactivated
Other definitions not permitted.
Max. single set weight
REAL
DBD004
90
Wizzard:
WB
nmax
*
Maximum set weight for a single
Inhibition time coarse
TIME
DBD008
500
0: deactivated
After switching the coarse signal on, no weight
evaluation is performed for the defined amount of
time (msec)!
Inhibition time fine
TIME
DBD012
500
0: deactivated
After switching the coarse signal off, no weight
evaluation is performed for the defined amount of
time (msec)!
Inhibition time Set-Act-
comparison
TIME
DBD016
0
After the command for starting the inhibition time,
the actual weight is not monitored during the
weighing procedure for the defined amount of
time.
Default value for analog
output with coarse
BYTE
DBB020
60
Analog output value if coarse signal active (in %)
Default value for analog
output with fine
BYTE
DBB021
40
Analog output value if fine signal active (in %)
Status output condition
TO2 TO1 Good TU1 TU2
Off
Net weight from TU1 to TO1
0
0
1
0
0
0
Net weight above TO1 to TO2
0
1
0
0
0
0
Net weight above TO2
1
0
0
0
0
1
Net weight from TU2 to under TU1
0
0
0
1
0
0
Net weight under TU2
0
0
0
0
1
1