
Operate
6.2 Parameter description
SITRANS VP300 with or without HART
80
Operating Instructions, 03/2011, A5E01258666-03
"2.2.6 DO 1 Pulse length"
Requirements:
Alarm module is installed. Positioner is in SIL mode"3.5.5 Activate
SIL mode" (Page 103)
Factory setting:
5 s
Setting options:
1 s
2 s
5 s
Purpose:
To output message dynamically.
Description:
Use this parameter to set the length of the pulse used to report a
successful partial stroke test in SIL mode.
"2.2.7 DO 2 Function" and "2.2.8 DO 3 Function"
Requirements:
Alarm unit is installed.
Factory setting:
With "DO 2 Function": A1; with "DO 3 Function": A2
Options:
Maintenance required
Maintenance demanded
Maintenance alarm
DI 1 Digital input
DI 2 Digital input
DI 3 Digital input
A1 Alarm limit
A2 Alarm limit
Deviation
Not in automatic mode
Output inverted
Purpose:
Specifying settings for output of error message and fault message.