Operate
6.2 Parameter description
SITRANS VP300 with or without HART
Operating Instructions, 03/2011, A5E01258666-03
63
"1.1.2 Tight closing"
Factory setting:
Off
Setting options:
Off
Up
Down
Up and down
Purpose:
Achieving optimum valve operation.
Description:
If the setpoint falls below the value for the lower tight closing limit or
exceeds the value for the upper tight closing limit, the valve is
moved into the valve seat with the maximum actuator force.
The tight closing function is activated on one end or for both end
positions. Make sure that the valve is not damaged when utilizing
the tight closing function. The values for the lower and upper tight
closing limits are factory-set.
The pre-set values can be changed with the following two
parameters:
"2.1.3 Lower tight closing limit" (Page 72)
"2.1.4 Upper tight closing limit" (Page 73)
"1.1.3 Initialize"
Requirements:
The actuator type for the respective installation is set.
"1.1.1 Actuator type" (Page 62)
Factory setting:
Cancel
Setting options:
Select "OK" to initialize the positioner.