Functions
8.3 Device delivery condition
SITRANS TH400
Operating Instructions, 06/2010, A5E01018688-02
33
8.3
Device delivery condition
The device parameters of the SITRANS TH400 - PA/FF are set to default values. You will
find the default settings in the relevant "Configuration Manuals".
When the SITRANS TH400 is delivered, the following parameters are set differently from the
default assignment:
Parameter
Set value
SITRANS TH400-PA (7NG3214)
Break monitoring, channel 1
ON
Short circuit monitoring, channel 1
OFF
SITRANS TH400-FF (7NG3215)
Break monitoring, channel 1
ON
Short circuit monitoring, channel 1
OFF
Excerpt of important default values for SITRANS TH400-PA and SITRANS TH400-FF
Sensor
Pt100 (IEC)
Connection type
Three-wire input
Unit
°C
Failure behavior
Last valid value
Filter time
0 s
Only for SITRANS TH400-PA devices
PA address
126
PROFIBUS identification
number
Manufacturer-specific
Only for SITRANS TH400-FF devices
Node address
22
Summary of Contents for SITRANS TH400
Page 30: ...Commissioning SITRANS TH400 30 Operating Instructions 06 2010 A5E01018688 02 ...
Page 36: ...Service and maintenance SITRANS TH400 36 Operating Instructions 06 2010 A5E01018688 02 ...
Page 44: ...Technical data SITRANS TH400 44 Operating Instructions 06 2010 A5E01018688 02 ...
Page 46: ...Dimension drawings SITRANS TH400 46 Operating Instructions 06 2010 A5E01018688 02 ...
Page 54: ...Appendix A 3 Technical support SITRANS TH400 54 Operating Instructions 06 2010 A5E01018688 02 ...
Page 60: ...Glossary SITRANS TH400 60 Operating Instructions 06 2010 A5E01018688 02 ...
Page 62: ...Index SITRANS TH400 62 Operating Instructions 06 2010 A5E01018688 02 ...