
Note
Improvement of interference immunity
• Lay signal cables separate from cables with voltages > 60 V.
• Use cables with twisted wires.
• Keep device and cables at a distance from strong electromagnetic fields.
• Take account of the conditions for communication specified in the Technical data (Page 193).
• Use shielded cables to guarantee the full specification according to HART/PA/FF/Modbus/
EIA-485/Profibus DP.
6.2
Connecting the TH100
Requirement
If you use stranded wire used, you need a ferrule.
Note the maximum permissible core cross-section (Page 194).
Procedure
1. Connect the input or inputs to terminals 3 to 6.
3-W
4
3
6
5
3W
Figure 6-1
2-wire, 3-wire or 4-wire RTD
2. Connect the supply voltage to the terminals 1 (+) and 2 (-).
Take the polarity into account. The device has reverse polarity protection.
s
1
2
6
+
-
P$
8
DX[
See also
Connecting
6.2 Connecting the TH100
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB
79