9.3.13
One-point calibration input 1 [14]
Calibrates the lower calibration point at input 1. The device moves the characteristic by the
difference between the original and the new calibration point. The result of the one-point
calibration is saved in the TRIM INPUT 1 parameter.
Indication on the dis‐
play:
TRIM INPUT 1
The two-point calibration via remote operation calibrates the low and high calibration point.
See also
Setting two-point calibration (Page 164)
Setting one-point calibration (Page 163)
9.3.14
One-point calibration input 2 [15]
Calibrates the lower calibration point at input 2. The device moves the characteristic by the
difference between the original and the new calibration point. The result of the one-point
calibration is saved in the TRIM INPUT 2 parameter.
Indication on the dis‐
play:
TRIM INPUT 2
The two-point calibration via remote operation calibrates the low and high calibration point.
See also
Setting two-point calibration (Page 164)
Setting one-point calibration (Page 163)
9.3.15
Change User PIN [16]
9.3.15.1
Change user PIN
Used to change the User PIN.
Setting range:
1 to 65535
Factory setting:
2457
Requirement
The "User PIN (Page 155)" parameter is enabled.
Parameter assignment
9.3 Parameter assignment over device with display
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
152