9.3.2
Connection type for input 1 [02]
Selects the connection type for input 1 depending on the selected sensor.
Indication on the dis‐
play
WIRING 1
Setting range:
2, 3, 4-wire
Factory setting:
3-wire
9.3.3
Wire resistance for connecting cable at Input 1 [03]
Requirement: Connection type 2-wire
Selects the wire resistance for Input 1.
Indication on the dis‐
play
WIRE RES 1
Setting range:
0 to 100 Ω
Factory setting:
0 Ω
9.3.4
Input type 2 [04]
Selects the input type 2.
Setting range:
Display
Meaning
NONE
No input type selected
P100I
Pt100 IEC751
P500I
Pt500 IEC751
P1k I
Pt1000 IEC751
TC B
1)
Thermocouple Type B IEC 584
TC E
1)
Thermocouple Type E IEC 584
TC J
1)
Thermocouple Type J IEC 584
TC K
1)
Thermocouple Type K IEC 584
TC N
1)
Thermocouple Type N IEC 584
TC R
1)
Thermocouple Type R IEC 584
TC S
1)
Thermocouple Type S IEC 584
TC T
1)
Thermocouple Type T IEC 584
TC L
1)
Thermocouple Type L IEC 584
Factory setting:
NONE
No input type selected
1)
Can only be selected when the input type TC was also selected for input 1.
Parameter assignment
9.3 Parameter assignment over device with display
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
142
Operating Instructions, 05/2020, A5E41864807-AB