The SITRANS TH200 and the SITRANS TH300 offer various runtime meters. Runtime
meters are used to monitor the connected process sequence.
1. Runtime meter for transmitter electronics
● Monitors the number of operating hours during which the transmitter remained in
continuous operation, depending on the ambient temperature.
● The operating hours sequence of the transmitter is recorded in 9 ambient temperature
ranges.
● Starts with the first commissioning at the factory.
● Runtime meter and temperature ranges cannot be reset or set by the user.
● The runtime meter is only updated if the device is in measuring mode. The runtime meter
is not updated in simulation mode.
2. Runtime meter for process variable
● Monitors the sequence of the sensor connected to the transmitter in various process
areas.
● The operating hours sequence of the process variable is recorded in 9 ranges. It is
subdivided according to the connected sensor and its sensor limits. The user cannot set
the ranges.
● The runtime meter is automatically reset if one of the following parameters is changed in
the device:
– Sensor class
– Sensor type
– Interface
– Sensor connection
– Sensor factor
The runtime meters can be read out using the parameterization software SIPROM T for
SITRANS TH200 or SIMATIC PDM or HART communicator for SITRANS TH300. The
runtime meters are automatically stored in the non-volatile memory once every hour. All
runtime meters are available again after the next restart if the device is disconnected from its
supply voltage.