Simulating signals
The block does not have a function for simulating process values.
16.2.4
Error handling of FbMr200
Error handling of FbMr200
The following errors can be displayed for this block:
● Higher-level error
● Module errors
Higher-level error
Higher-level errors are indicated by the value 1 at output parameter
QRackF
if the signal state
in the HighWord of input parameter
Mode
changes to a value other than 16#80, or if
input
RackF
is set.
The Bad output is set in addition
Module errors
If an incorrect module ID of the connected DP slave is read from the block, output
QModF
will
be set. The Quality Codes are set to 16#00 , similar to the higher-level error.
16.2.5
FbMr200 message
Messaging
This block does not offer messaging.
16.2.6
I/Os of FbMr200
Input parameters
Parameter
Description
Type
Default
AddrPV
AI address
INT
0
Addr
Addresses in the process image
STRUCT
1)
0
SubnTyp
1 = external DP interface
BOOL
0
RackF
1 = DP slave failure (rack fault)
BOOL
0
TexRef
Text reference for external messages
WORD
16#00
MultiRanger 200
16.2 FbMr200
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
771