The corresponding message is suppressed using the parameters:
●
PV/SV/TV/QV_AH_MsgEn
= 0: Alarm (high) messages are suppressed
●
PV/SV/TV/QV_AL_MsgEn
= 0: Alarm (low) messages are suppressed
●
PV/SV/TV/QV_WH_MsgEn
= 0: Warning (high) messages are suppressed
●
PV/SV/TV/QV_WL_MsgEn
= 0: Warning (low) messages are suppressed
You can define a hysteresis (
PV/SV/TV/QV_Hyst
) for the limits, for example to suppress
signal flatter. You can also modify the limits and hysteresis via the faceplate.
Gradient monitoring
The gradient
PV_Grad
is calculated by means of a delay function configurable using
LagTime
.
During calculation of the gradient, jumps in the input value
PV_In
are smoothed.
The peak values of the gradient are output in the output parameters
PV_GradNP
(negative
gradient) and
PV_GradPP
(positive gradient). These are reset when the operator enters the
corresponding command for resetting.
The slope of the gradient
PV_Grad
can be monitored for the following limits:
● Limit (high) for the positive gradient (
GradHUpLim
)
● Limit (high) for the negative gradient (
GradHDnLim
)
● Limit (low) for the absolute gradient (
GradLLim
)
Activation of the individual monitoring functions is carried out at the corresponding "Enable"
parameters, e.g.
GradHUpEn
for activating the high gradient limit for positive gradients
(
GradHUpLim
).
Reaching or violation of your defined limits is indicated at the corresponding "Active" output
parameters, e.g. by means of
GradHUpAct
= 1 for the limit (high) for the positive gradient.
Messages can be output for these alarms. You can activate these as follows:
● Message for alarms (high) for the positive gradient:
GradHUpMsgEn
= 1
● Message for alarms (high) for the negative gradient:
GradHDnMsgEn
= 1
● Message for alarms (low) for the absolute gradient:
GradLMsgEn
= 1
Suppressing messages using the
MsgLock
parameter
This block provides the standard "Suppressing messages using the
MsgLock
parameter"
function that is described in the APL Online Help.
Bypass function
This block provides the standard function Interlocking functions (Page 13).
SITRANS FC430
12.1 SitrFC43
SITRANS Library for PCS 7
470
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...