The following errors can be displayed for this block:
● Error numbers
● Control system fault (
CSF
)
Overview of error numbers
The I/Os
Error0Num
(process value
PV
) and
Error1Num
(totalizer value
Tot
) can be used
to output the following error numbers:
Error number
Meaning of the error number
-1
Predefined value when inserting the block; the block is not executed.
0
There is no error.
30
The process value/totalizer value cannot be displayed in the REAL number field
Control system fault (CSF)
An external signal can be activated via the
CSF
input. A process control error is triggered if this
signal = 1. Refer to the "Error handling" chapter in the APL Online Help.
11.1.5
I/Os of SitrP_PA
Input parameters
Parameter
Description
Type
Default
DevType
Device type of SITRANS P
1: SitransP DSIII PA
1: SitransP P300 PA
INT
0
PV
Process value
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
Tot
Totalizer value
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
PV_Meas*
Measured value that is interconnected at the
PV
input:
0: <invalid value>
1: Pressure
2: Volume flow
3: Mass flow
4: Fill level
5: Volume
6: Pressure (untrimmed)
7: Sensor temperature
8: Electronics temperature
BYTE
0
SITRANS P PA
11.1 SitrP_PA
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
431