6.1.6
Lut400 connections
Input parameters
Parameter
Description
Type
Default
SlotHart
Slot number of the Lut400 within the AI
module in the ET 200M from HW Config
INT
0
VarHart
Selection of the HART variables config‐
ured in HW Config:
0: No HART variable
1: PV
2: PV and SV
3: PV, SV and TV
4: PV, SV, TV and QV
INT
4
BypLiOp
1 = Bypass commands via interconnec‐
tion
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
BypPVOp
1 = Select bypass PV (via operator)
BOOL
0
RstBypOp
1 = Reset bypass PV (via operator)
BOOL
0
BypPVLi
1 = Select bypass PV (via interconnec‐
tion)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
RstBypLi
1 = Reset bypass PV (via interconnec‐
tion)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
BypPV
Substitution value if block is in bypass
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
BypLock
1 = Bypass activation or deactivation is
locked for operator
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
PV_In
Process value (4 to 20 mA signal)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
PV
First HART variable (primary variable)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
SV
Second HART variable (secondary vari‐
able)
STRUCT
● Value : REAL
● ST: BYTE
-
0.0
● 16#80
TV
Third HART variable (tertiary variable)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
SITRANS LUT400
6.1 Lut400
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11