Operate
6.2 Parameter description
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
69
6.2.2
"1 Quickstart"
6.2.2.1
"1.1 Commissioning"
"1.1.1 " in preparation
"1.1.2 PV Select"
Factory setting:
Pressure
Setting range:
•
Pressure
•
Volume flow
•
Mass flow
•
Level
•
Volume
•
Mass
•
User characteristic
Purpose:
Selection of the measuring mode
Description:
Select the measuring mode with the measuring mode switch. Depending on
the selection made here, menu commands that are not relevant can be
shown or hidden. The values are defined in the following menu commands.
"1.1.3 Measuring Range"
"1.1.3.1 Setting Blind"
"1.1.3.1.1 Pressure Unit"
Factory setting:
mbar
Setting range:
inH
2
O, inHg, ftH
2
O, mmH
2
O, mmHg, psi, bar, mbar, g/cm
2
, kg/cm
2
, Pa, kPa,
HPa, Torr, atm, MPa, inH
2
O (4 °C), mmH
2
O (4 °C)
Purpose:
Selection of the unit for the pressure parameter
Description:
This parameter allows you to select the unit for the measured pressure
value. The parameters associated with this unit are automatically converted
to the new unit.
"1.1.3.1.2 Setting LRV"
Factory setting:
0 mbar, or as specified when ordered
Setting range:
Sensor limits