Alarm, error and system messages
9.2 Messages
SITRANS P500 with HART
188
Operating Instructions, 12/2014, A5E02344528-09
Icon
Error message
Cause/ measures
Sensor service request
Service the sensor without delay or reset the service timer.
"3.5.2.2 Timer" (Page 128)
Pressure measurement value unre-
liable
Check the further messages.
Sensor temperature limit exceeded
/ undershot
This condition can lead to damage to the pressure transmitter.
Pressure out of the sensor measur-
ing range
This condition can lead to damage to the pressure transmitter. Check your
application.
"3.7 MinMaxPointer" (Page 130)
Static pressure out of the measur-
ing range
This condition can lead to damage to the pressure transmitter. Check your
application.
Device temperature out of specifi-
cations
Permissible ambient temperature exceeded. This can lead to damage to the
pressure transmitter.
Current saturation alarm
Output current is in the saturation range. Check the set measuring range
limits.
"2.1.2 Measuring Range" (Page 84)
Lower alarm limit value LOLO
The value that you set has been undershot.
Upper alarm limit value HIHI
The value that you set has been exceeded.
Lower warning limit value LO
The value that you set has been undershot.
Upper warning limit value HI
The value that you set has been exceeded.
See also
"2.4.3 Trim" (Page 106)
"2.4.3.1 DA-Converter" (Page 106)