4. Open the cover of the buttons:
Figure 8-2
Top view
5. Operate the buttons as follows:
Apply lower range value (with pressure applied) Hold down the button
for 3 seconds.
Apply upper range value (with pressure applied) Hold down the button
for 3 seconds.
Zero point adjustment
Hold down the buttons and for 3 seconds.
Set Upper fault current
Hold down the button
for 3 seconds.
Set Lower fault current
Hold down the button
for 3 seconds.
Additional functions are available with remote operation.
Parameter assignment (Page 97)
8.5
Application examples
8.5.1
gauge pressure, absolute pressure from the differential pressure series and
absolute pressure from the gauge pressure series
8.5.1.1
Commissioning for gases
Requirement
All valves are closed.
Commissioning
8.5 Application examples