Absolute pressure measuring limits from
gauge pressure series
Upper measuring limit
100% of max. range (for oxygen measurement: max. 100 bar/10 MPa/
1450 psi and 60 °C ambient temperature/medium temperature)
Lower range value
Between the measuring limits (continuously adjustable)
13.1.5
Absolute pressure with front-flush diaphragm
Absolute pressure with front-flush diaphragm
Measured variable
Absolute pressure
Measuring span (continuous‐
ly adjustable) or measuring
range, max. operating pres‐
sure and max. test pressure
Measuring span
Maximum permissible
operating pressure MAWP
(PS)
Maximum test
pressure
43 … 1300 mbar a
4.3 ... 130 kPa a
17 … 525 inH
2
O a
Refer to the information on the nameplate of the pressure
transmitter and the data on the mounting flange
1)
166 … 5000 mbar a
16.6 ... 500 kPa a
2.41 … 72.5 psi a
1 … 30 bar a
0.1 ... 3 MPa a
14.5 … 435 psi a
Depending on the process connection, the measuring span may differ from these values
1)
The MAWP value of the pressure transmitter can be lower than the PN value of the mounting
flange and vice versa. To determine the maximum permissible operating pressure and the
maximum permissible test pressure, use the lowest value as reference.
Absolute pressure measuring limits with front-flush diaphragm
Lower measuring limit
● Measuring cell with silicone oil filling
0 mbar a/kPa a/psi a
Upper measuring limit
100% of max. range
Lower range value
Between the measuring limits (continuously adjustable)
Technical data
13.1 Input
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
195