Sensor trim at the upper trim point
1. Apply the pressure for the upper sensor trim at the device.
The upper trim point needs to be greater than the lower trim point.
2. Use the "Apply values" menu to enter the pressure value that you have created and assign
the pressure value to the device.
The device calibrates to your value.
The slope of the characteristic curve is corrected.
The lower sensor trim point is not affected by this.
Result