Operating functions via HART
7.12 Setting the current limits
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02
7-19
See also
7.12
Setting the current limits
Description
The level of the upper and lower fault current and the upper and lower saturation limits can
be freely selected within the preset limits of the current output signal.
The specified accuracy of the current output signal is only valid within the current limits 4 to
20 mA.
S>@
,
$
>P$@
0HDVXULQJUDQJH
Figure 7-10 Current limits
(1)
Linear control range
(2)
Lower saturation limit (default value)
(3)
Upper saturation limit (default value)
(4)
Lower fault current value (default value)
(5)
Upper fault current value (default value)
(6)
Recommended setting range for lower fault current range and lower control range limit
(7)
Recommended setting range for upper fault current range and upper control range limit