
Example
For the volume measurement, you set the following values, for example:
Damping value:
2.0 s
Lower range value:
0.0 mbar
Upper range value:
500.0 mbar
Application:
Cylinder vessel (CYLIN)
Unit:
m
3
Lower scaling point:
0.0 m
3
Upper scaling point:
10.0 m
3
9.2.4.5
Set application
Procedure
1. Navigate to the parameter view.
Navigating in the views (Page 76)
2. Select the "Application" parameter [05].
3. Select the parameter value.
9.2.5
Application point [06]
Sets the application point from which scaling occurs according to the square root. Before the
application point, the scaling occurs in a linear relationship with the differential pressure.
This parameter is only visible when you have selected the characteristic curve "Linear, square
root" (VSLIN or MSLIN) using the "Application" parameter.
Setting range:
5 to 15%
Factory setting:
10%
See also
Volume and mass flow measurements (Page 115)
9.2.6
Zero point adjustment [07]
Introduction
A series of factors, such as installation, static pressure, temperature or long-term stability, can
cause zero-point errors.
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
119