SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
57
Quick Start
Note
•
The Quick Start Wizard settings are inter-related and changes apply only after you click
on FINISH AND DOWNLOAD at the end of step 5 to save settings offline and transfer
them to the device.
•
Do not use the Quick Start Wizard to modify individual parameters. For quick access to
echo profile parameters see Echo Setup (Page 69), or see Parameter Reference
(Page 97) for a complete list.
•
Click on BACK to return and revise settings or CANCEL to exit the Quick Start.
•
For a vessel with obstructions see Auto False Echo Suppression (Page 67).
Launch SIMATIC PDM, open the menu Device – Wizard - Quick Start, and follow steps 1 to
5.
①
Quick Start
Step 1 - Identification
Note
The layout of the dialog boxes shown may vary according to the resolution setting for your
computer monitor.
1.
Click on Read Data from Device to upload Quick Start parameter settings from the device
to the PC/PG and ensure PDM is synchronized with the device.
2.
If required, change the language for the local user interface.
3.
Click on NEXT to accept the default values. (Description, Message, and Installation Date
fields can be left blank.)