SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
119
7.2.7.9
Measured values (2.8.9.)
Read only. Allows you to view measured values for diagnostic purposes. In SIMATIC PDM,
open the menu View - Process Variables.
LEVEL MEASUREMENT (2.8.9.1.)
The value for level
SPACE MEASUREMENT (2.8.9.2.)
The value for space
DISTANCE MEASUREMENT (2.8.9.3.)
The value for distance
VOLUME MEASUREMENT (2.8.9.4.)
The value for volume
7.3
Diagnostics (3.)
7.3.1
Echo profile (3.1.)
Allows you to request the current echo profile either locally via the handheld programmer, or
remotely.
To request a profile via the handheld programmer:
1.
In PROGRAM mode, navigate to Diagnostics (3.) > Echo profile (3.1.).
2.
Press RIGHT arrow to request a profile.
For more detail, refer to Requesting an Echo Profile (Page 46).
To request a profile via SIMATIC PDM:
1.
Open the menu Device – Echo Profile Utilities.
2.
For more detail, refer to Echo profile utilities (Page 65).
To request a profile via AMS Device Manager:
Refer to Echo Profile (Page 87).